ADFR
Emergency-Lighting Batteries Lanterns Exit-Signs Accessories
 

S6L

Series Features

  • ANSI/IEEE Std. 344-1975
  • ANSI/ASME N45.2/N46.2-1977
  • NUREG-0800: 9.5.1 Fire Protection Prog.
  • ISA: 13 (14-22)-1974
  • Integrated Solid State System & Switching
  • Three-Rate, Controlled, Automatic Charger ~ No manual battery recycling
  • Brownout Sensitivity
  • Fused AC Input and DC Output Circuit Protection
  • Single Voltage Transformer for
    120 VAC Operation
  • Maximum Input Rating
    120VAC, 60 Hz, 1.0 Amps

S6L

Shown in standard two tone beige & cocoa finish

 
  • Seismic Rated, Lead Acid Battery
  • Dry Charge for 5 year shelf life
  • Flame Arrestor Vent Caps
  • 32 degrees ~ 105 degrees F Operation Range
  • 6 Volt Operation
  • 8-12 Year Operating Life
  • Par-46 Sealed Beam Lamps
  • STD Lamp: 6 Volt ~ 21 Watt
 
  • Rugged 20 gauge Steel Housing
  • Top End Battery Access
  • Battery Viewport
  • Full Length Piano Hinge with Lock Hasp
  • Seismic Rated Wall Mounting Shelf
  • Two Tone Powder Coat Finish (Beige & Cocoa) Standard
  • Slide Out Control Chassis
  • Test Switch
  • Voltmeter
  • Load Cutoff Switch
  • Amber (Power On), Red (Hi-Charge), & Green (Trickle Charge) Indicators
  • Hydrometer Disk Indicators
  • UL Listed
 
Height: 20.5"
Width: 18.5"
Depth: 8.5"
 

The S6L is our exclusive industrial grade battery system with a seismic qualification. Designed for use in nuclear and other maximum safety installations, the refillable lead acid batery provides up to 8 hours of operation with a 3 lamp head load.

 

Unit Information (Watts per hour)

Model #

STD LAMP WATT

1.5

2

3

4

5

6

7

8

Replacement Battery

2S6L100-80

21

120

120

120

120

105

90

75

60

(1) L6100S

Illumination is rated to 87.5% of nominal system voltage and recharge to full capacity within 24 hours.
NEC requires 1.5 hours of emergency illumination.

 

 