ADFR
Emergency-Lighting Batteries Lanterns Exit-Signs Accessories
 

AR

Series Features

  • Integrated Solid State System
  • Multi-Rate, Controlled, Automatic Charger ~ No manual battery recycling
  • Low Voltage Battery Cutoff
  • Brownout Sensitivity
  • Fused AC Input & DC Output Circuit Protection
  • Dual Voltage Transformer for
    120 VAC Operation
  • Maximum Input Rating
    120VAC, 60 Hz, 0.35 Amps
    277VAC, 60 Hz, 0.15 Amps

AR

Shown in Standard Beige Finish

 
  • Refillable Lead Acid Battery
  • 32 degrees F ~ 105 degrees F Operating Range
  • 6 Volt Operation
  • 8-12 Year Operating Life
  • Par-36 Sealed Beam Lamps
  • STD Lamps: 6 Volt ~ 25 Watt
 
  • Rugged 20 gauge Steel Housing
  • Top End Battery Access
  • Keyhole Mount Std. or Order Shelf #23
  • Beige Powder Coat Finish Standard
  • Test Switch
  • Red (Hi-Charge) & Green (Trickle Charge) Indicators
  • UL Listed
 
Height: 12.7"
Width: 11.9"
Depth: 4.9"
 

The AR Series is equipped with a refillable lead acid battery, providing 8 to 12 years of servie in ambient temperatures ranging from 32 degrees F to 105 degrees F.

 

Unit Information (Watts per hour)

Model #

STD LAMP WATT

1.5

2

3

4

5

6

7

8

Replacement Battery

2AR6L40

25

120

90

60

45

36

30

26

23

(1) L640

H2AR6L40***

20

120

90

60

45

36

30

26

23

(1) L640

***Chicago Code Approved

Illumination is rated to 87.5% of nominal system voltage and recharge to full capacity within 24 hours.
NEC requires 1.5 hours of emergency illumination.

 

 